4 fault detection – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 135

Advertising
background image

Digital Operator Display

Fault Name

oFA01

Option Unit Fault
Replace the option unit.

Cause

Possible Solution

The option unit is not connected

properly to the drive.

Turn the power off and reconnect the option unit.

Digital Operator Display

Fault Name

oH1

Overheat 1 (Heatsink Overheat)
The temperature of the heatsink has exceeded the overheat pre-alarm level.

Cause

Possible Solution

Surrounding temperature is too

high.

• Check the temperature surrounding the drive.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.

Load is too heavy.

• Measure the output current.
• Lower the carrier frequency (C6-02).
• Reduce the load.

Current flowing to control circuit

terminal +V exceeded the tolerance

level.

• Check the current level of the terminal.
• Set the current to the control circuit terminal to be 20 mA or less.

Digital Operator Display

Fault Name

oL1

Motor Overload
The electrothermal sensor tripped overload protection.

Note: The integrated value of the internal register for oL1 must decrease before

oL1 can be reset.

Cause

Possible Solution

Load is too heavy.

Reduce the load.

Cycle times are too short during

acceleration and deceleration.

Increase the acceleration and deceleration times (C1-01 through C1-04).

• Drive overloaded at low

speeds.

• Overload may occur at low

speeds when using a general-

purpose motor, even if

operating within the rated

current limitation.

• Reduce the load.
• Increase the speed.
• If the drive is supposed to operate at low speeds, either increase the motor

capacity or use a motor specifically designed to operate with the drive.

Although a special type of motor is

being used, the motor protection

selection is set for a general-

purpose motor (L1-01 = 1).

Set L1-01 to 2.

5.4 Fault Detection

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

135

5

Troubleshooting

Advertising