7 control circuit wiring, Control circuit wiring, J1000 – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 52

Advertising
background image

3.7

Control Circuit Wiring

NOTICE: Do not solder the ends of wire connections to the drive. Soldered wire connections can loosen over

time. Improper wiring practices could result in drive malfunction due to loose terminal connections.

S1

S2

S3

S4

S5

24 V

I

V

+24

V 8

mA

SC

AM

AC

+

-

AM

+V

A1

AC

2 k

MA

MB

MC

Forward run/stop

Reverse run/stop

External fault

Fault reset

Digital inputs
(default setting)

J1000

Control circuit

Multi-step
speed 1
main/aux switch

DIP switch S1

Option unit

connector

<1>

DIP
switch S3

Shield ground

terminal

0 to +10 V (20 k )

(0)4 to 20 mA (250 )

Setting power supply
+10.5 max. 20 mA

Digital output
250 Vac, 10 mA to 1 A
30 Vdc, 10 mA to 1 A
(default setting)

Main speed
frequency
reference.
Multi-function
programmable

Sink

Source

<2>

<3>

0 to +10 Vdc
(2 mA)

Analog monitor
output

Monitor
output

main circuit terminal

shielded line

twisted-pair shielded line

control terminal

Figure 3.10 Control Circuit Connection Diagram

<1> Connected using sequence input signal (S1 to S5) from NPN transistor; Default: sink

mode (0 V com)
<2> Use only the +24 V internal power supply in sinking mode; the source mode requires an

external power supply.

Refer to I/O Connections on page 59

.

3.7 Control Circuit Wiring

52

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide