Multi-step speed operation (4-step speed), Multi-step speed operation parameters, 5 basic operation – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 97

Advertising
background image

Table 4.5 Drives with Heavy Duty Default Carrier Frequency of 10 kHz

200 V Single Phase Units

200 V Three Phase Units

Drive

Model

Rated Current [A]

Drive

Model

Rated Current [A]

2 kHz

10 kHz

15 kHz

2 kHz

10 kHz

15 kHz

BA0001

1.2

0.8

0.6

2A0001

1.2

0.8

0.6

BA0002

1.9

1.6

1.3

2A0002

1.9

1.6

1.3

BA0003

3.5

3.0

2.4

2A0004

3.5

3.0

2.4

BA0006

6.0

5.0

4.0

2A0006

6.0

5.0

4.0

Table 4.6 Drives with Heavy Duty Default Carrier Frequency of 8 kHz

200 V Single Phase Units

200 V Three Phase Units

400 V Three Phase Units

Drive

Model

Rated Current [A]

Drive

Model

Rated Current [A]

Drive

Model

Rated Current [A]

2 kHz

8 kHz 15 kHz

2 kHz

8 kHz 15 kHz

2 kHz

8 kHz 15 kHz

BA0010

9.6

8.0

6.4

4A0001

1.2

1.2

0.7

2A0010

9.6

8.0

6.4

4A0002

2.1

1.8

1.1

2A0012

12.0

11.0

8.8

4A0004

4.1

3.4

2.0

4A0005

5.4

4.8

2.9

2A0020

19.6

17.5

14.0

4A0007

6.9

5.5

3.3

4A0009

8.8

7.2

4.3

4A0011

11.1

9.2

5.5

u

Multi-Step Speed Operation (4-Step Speed)

Select up to 9 preset references (including Jog reference) using two multi-function inputs S4

and S5. Two multi-step references can be selected using two multi-function inputs as

illustrated in

Figure 4.14

.

n

Multi-Step Speed Operation Parameters

No.

Name

Description

d1-01 Frequency Reference 1

Frequency reference. o1-03 determines the units, with Hz as the default.

d1-02 Frequency Reference 2

Frequency reference when multi-function input “Multi-Step Speed Reference 1"

(H1- = 3) is on. Setting unit: set by o1-03.

d1-03 Frequency Reference 3

Frequency reference when multi-function input “Multi-Step Speed Reference 2”

(H1- = 4) is on. Setting unit: set by o1-03.

d1-04 Frequency Reference 4

Frequency reference when multi-function input “Multi-Step Speed Reference 1,

2" (H1- = 3 and 4) are both on. Setting unit: set by o1-03.

4.5 Basic Operation

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

97

4

Start-Up Programming & Operation