3.11 Interlocking with Connected Machinery

For safety reasons, applications that may be affected by the operation status of the drive should

be set up so that operation can only occur when the drive is ready to operate. A "Drive ready"

and "Fault" signal should be assigned to the multi-function outputs to guarantee interlock with

application.

u

Drive Ready Signal

When the “Drive ready” signal has been set to one of the multi-function contact outputs, that

output will close whenever the drive is ready to accept a Run command or is already running.

Under the following conditions the Drive ready signal will switch off and remain off, even if

a Run command is entered:
• when the power supply is shut off
• during a fault
• when there is problem with the control power supply
• when a parameter setting error makes the drive unable to run even if a Run command has

been entered

• when a fault such as overvoltage or undervoltage is triggered as soon as the Run command

is entered

• when the drive is in the Programming mode and will not accept a Run command even when

entered.

3.11 Interlocking with Connected Machinery

66