Drive motor overload protection – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 260

Advertising
background image

n

Low Voltage Wiring for Control Circuit Terminals

Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local

codes for wiring. The external power supply shall be a UL-Listed Class 2 power source or

equivalent.

Table C.12 Control Circuit Terminal Power Supply

Input / Output

Terminal Signal

Power Supply Specifications

Multi-function digital inputs

S1, S2, S3, S4, S5, SC

Use the internal power supply of the drive.

Use class 2 for external power supply.

Main frequency reference

+V, A1, AC

Use the internal power supply of the drive.

Use class 2 for external power supply.

n

Drive Short-Circuit Rating

This drive has undergone the UL short-circuit test, which certifies that during a short circuit

in the power supply the current flow will not rise above 31,000 amps maximum at 240 V for

200 V class drives and 480 V for 400 V class drives.
• The MCCB and breaker protection and fuse ratings shall be equal to or greater than the

short-circuit tolerance of the power supply being used.

• Suitable for use on a circuit capable of delivering not more than 31,000 RMS symmetrical

amperes for 240 V in 200 V class drives (up to 480 V for 400 V class drives) motor overload

protection.

u

Drive Motor Overload Protection

Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload

protection. The internal motor overload protection is UL listed and in accordance with the

NEC and CEC.

n

E2-01: Motor Rated Current

Setting Range: Model Dependent
Default Setting: Model Dependent
Parameter E2-01 (motor rated current) protects the motor if parameter L1-01 is not set to 0

(default is 1, standard induction motor protection enabled).

n

L1-01: Motor Overload Protection Selection

The drive has an electronic overload protection function (oL1) based on time, output current

and output frequency, which protects the motor from overheating. The electronic thermal

overload function is UL-recognized, so it does not require an external thermal overload relay

for single motor operation.
This parameter selects the motor overload curve used according to the type of motor applied.

C.3 UL Standards

260

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide