Table c.9, Are yaskawa, C.3 ul standards – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 256

Advertising
background image

Drive

Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range
AWG, kcmil

Screw Size

Tightening

Torque

N•m (lb.in.)

2A0012

R/L1, S/L2, T/L3

12

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

14

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

10

14 to 10

2A0020

R/L1, S/L2, T/L3

10

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

10

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

10

14 to 10

Table C.9 Wire Gauge and Torque Specifications

Drive

Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range
AWG, kcmil

Screw Size

Tightening

Torque

N•m (lb.in.)

4A0001
4A0002
4A0004

R/L1, S/L2, T/L3

14

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

14

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

14

14 to 10

4A0005
4A0007
4A0009

R/L1, S/L2, T/L3

14

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

14

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

10

14 to 10

4A0011

R/L1, S/L2, T/L3

12

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

14

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

10

14 to 10

Note:

Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a

continuous maximum allowable temperature of 75 °C 600 V UL approved vinyl sheathed insulation.

Ambient temperature should not exceed 30 °C.

C.3 UL Standards

256

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

Advertising