3.3

Main Circuit Connection Diagram

Refer to diagrams in this section for the Main Circuit wiring connections. Connections may

vary based on drive capacity. The main circuit DC power supply powers the control circuit.

NOTICE: Do not use the negative DC bus terminal “-” as a ground terminal. This terminal is at high voltage

DC potential. Improper wiring connections could result in damage to the drive.

u

Single-Phase 200 V Class Models BA0001 to BA0010

Drive

Jumper

Single-phase
200 Vac

Motor

DC link choke

(option)

Braking Resistor
Unit (option)

R/L1

S/L2

+1

+2

B1 B2

U/T1
V/T2
W/T3

Figure 3.3 Connecting Single-Phase Main Circuit Terminals

NOTICE: Do not connect T/L3 terminal when using single-phase power supply input. Incorrect wiring may

damage the drive.

u

Three-Phase 200 V Class Models 2A0001 to 2A0020
Three-Phase 400 V Class Models 4A0001 to 4A0011

Drive

Motor

Three phase 200 Vac

(400 Vac)

Braking
Resistor Unit

(option)

R/L1
S/L2
T/L3

U/T1
V/T2
W/T3

B1 B2

Jumper

DC link choke

(option)

+1

+2

Figure 3.4 Connecting Three-Phase Main Circuit Terminals

3.3 Main Circuit Connection Diagram