Application parameters configure the Run Command Source, DC Injection Braking, and other

application-related settings.

No.

Name

Description

Range Def. Mode Addr.

Hex

Pg.

b1: Operation Mode Selection

Use b1 parameters to configure the operation mode.

b1-01

Frequency

Reference

Selection

Selects the frequency reference input source.

0: Digital Operator - Digital preset speed d1-01 to

d1-08

1: Terminals - Analog input terminal A1

2: MEMOBUS/Modbus communications (option)

3: Potentiometer (option)

0 to 3

1

S

180

88

b1-02

Run

Command

Selection

Selects the run command input source.

0: Digital Operator - RUN and STOP keys on the

digital operator

1: Digital input terminals

2: MEMOBUS/Modbus communications (option)

0 to 2

1

S

181

90

b1-03

Stopping

Method

Selection

Selects the stopping method when the run command

is removed.

0: Ramp to Stop

1: Coast to Stop

0, 1

0

S

182

92

b1-04

Reverse

Operation

Selection

Permits or prohibits reverse operation.

0: Reverse enabled.

1: Reverse disabled.

0, 1

0

O

183

b1-07

LOCAL/

REMOTE Run

Selection

Determines the operation when the Run command

source is switched from LOCAL to REMOTE or

between REMOTE and MEMOBUS/Modbus

communication.

0: External Run command has to be cycled at the new

source to be activated.

1: External Run command at new source is accepted

immediately.

0, 1

0

O

186

b1-08

Run

Command

Selection

while in

Programming

Mode

0: Run command accepted only in the operation

menu.

1: Run command accepted in all menus.

2: Prohibit entering Programming Mode during Run

0 to 2

0

O

187

b1-14 Phase Order

Selection

Sets the phase order for drive output terminals U/T1,

V/T2 and W/T3.

0 : Standard

1 : Switch phase order

0, 1

0

O

1C3

b1-17

Run

Command at

Power Up

Determines the operation when a Run command is

active at power up of the drive.

0: Run command not issued, needs to be cycled

1: Run command issued, motor operation start

0, 1

0

O

1C6

B.2 Parameter Table

216