B.2 parameter table – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 232

Advertising
background image

No.

Name

Description

Range Def. Mode Addr.

Hex

Pg.

L8-05

Input Phase

Loss

Protection

Selection

Selects the detection of input current phase loss,

power supply voltage imbalance, or main circuit

electrolytic capacitor deterioration.

0: Disabled

1: Enabled

Note: This parameter is disabled in 200 V single-

phase drives.

0, 1

1

O

4B1

L8-10

Heatsink

Cooling Fan

Operation

Selection

Controls the heatsink cooling fan operation.

0: Run with timer (Fan operates only during run and

for 60 seconds after stop.)

1: Run always (Cooling fan operates whenever the

drive is powered up.)

0, 1

0

O

4B6

L8-12 Ambient

Temperature

Setting

Used to input the ambient temperature. This value

adjusts the drive oL2 detection level.

-10 to

50

30 °C

O

4B8

L8-18 Soft Current

Limit

Selection

Selects the software current limit function. Typically

no adjustment is required.

0: Disabled

1: Enabled

0, 1

1

O

4BE

L8-35

<3>

Installation

Method

Selection

Selects the installation type:

0: IP20/IP00 Drive

1: Side-by-Side Mounting

2: NEMA Type 1 Drive

3: Finless Drive or External Heatsink Installation

0 to 3

0

O

4EC

L8-38 Carrier

Frequency

Reduction

Provides protection to the IGBTs by reducing the

carrier frequency at low speeds.

0: Disabled

1: Enabled below 6 Hz

2: Enabled for the whole speed range

Current

C6-02

Carrier Frequency

ND
HD

2

0

200 V Single Phase

80% of HD

10 (8)

15

400 V: 60% of HD

0 to 2

1

O

4EF

<1>

When enabled, the drive stops accelerating when it exceeds the value of L3-02, Stall Prevention Level. The drive
decelerates after 100 ms and begins accelerating again after restoring the current level.

<2>

Default setting value is 120% when C6-01 is set to 1 (ND) and 150% when C6-01 is set to 0 (HD).

<3>

This parameter is not reset to the default value when the drive is reinitialized using A1-03.

<4>

The default setting and the upper limit of the setting range are determined by C6-01, Drive Duty Mode, and
L8-38, Carrier Frequency Reduction Selection.

B.2 Parameter Table

232