Table 3.2, Single-phase 200 v class, Three-phase 200 v class – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 47: 6 main circuit wiring

Advertising
background image

Refer to UL Standards Compliance on page 254

for information on UL compliance.

n

Single-Phase 200 V Class

Table 3.2 Wire Gauge and Torque Specifications

Drive

Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range
AWG, kcmil

Screw Size

Tightening

Torque

N•m (lb.in.)

BA0001
BA0002
BA0003

R/L1, S/L2, T/L3

14

18 to 14

M3.5

0.8 to 1.0

(7.1 to 8.9)

U/T1, V/T2, W/T3

14

18 to 14

⊖, ⊕1, ⊕2

18 to 14

B1, B2

18 to 14

14

18 to 14

BA0006

R/L1, S/L2, T/L3

12

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

14

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

10

14 to 10

BA0010

R/L1, S/L2, T/L3

10

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

14

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

10

14 to 10

n

Three-Phase 200 V Class

Table 3.3 Wire Gauge and Torque Specifications

Drive

Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range
AWG, kcmil

Screw Size

Tightening

Torque

N•m (lb.in.)

2A0001
2A0002
2A0004
2A0006

R/L1, S/L2, T/L3

14

18 to 14

M3.5

0.8 to 1.0

(7.1 to 8.9)

U/T1, V/T2, W/T3

14

18 to 14

⊖, ⊕1, ⊕2

18 to 14

B1, B2

18 to 14

14

18 to 14

3.6 Main Circuit Wiring

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

47

3

Electrical Installation

Advertising