4 fault detection – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 140

Advertising
background image

Digital Operator Display

Fault Name

There is a problem with the voltage

from the drive input power.

• Check the voltage.
• Correct the voltage to within range listed in drive input power specifications.

The power has been interrupted.

Correct the drive input power.

Drive internal circuitry has become

worn.

• Check the maintenance time for the capacitors (U4-05).
• Replace the drive if U4-05 exceeds 90%.

The drive input power transformer

is not large enough and voltage

drops after switching on power.

Check the capacity of the drive input power transformer.

Air inside the drive is too hot.

Check the drive internal temperature.

Problem with the CHARGE

indicator.

Replace the drive.

Digital Operator Display

Fault Name

Uv3

Undervoltage 3 (Inrush Prevention Circuit Fault)
The inrush prevention circuit has failed.

Cause

Possible Solution

The contactor on the inrush

prevention circuit is damaged.

• Cycle power to the drive. Check if the fault reoccurs.
• Replace the drive if the fault continues to occur.
• Check monitor U4-06 for the performance life of the inrush prevention circuit.
• Replace the drive if U4-06 exceeds 90%.

5.4 Fault Detection

140

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide