Transistor Input Signal Using +24 V Common/Source Mode

When controlling digital inputs by PNP transistors (+24 V common/sourcing mode), set the

DIP switch S3 to SOURCE and use an external 24 V power supply.

S1

+24V

S2

S3

+24V

S4

S5

SC

S3

SINK

SOURCE

SINK

SOURCE

External
power supply

FWD Run/Stop

REV Run/Stop

External Fault N.O.

Fault reset

Multi-step speed 1

Shielded cable

Figure 3.18 Source Mode: Sequence from PNP Transistor (+24 V Common)