4 fault detection – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 136

Advertising
background image

Digital Operator Display

Fault Name

Voltage is too high for the V/f

characteristics.

• Adjust the user set V/f patterns (E1-04 through E1-10). Parameters E1-08 and

E1-10 may need to be reduced.

• If E1-08 and E1-10 are set too high, there may be very little load tolerance at

low speed.

The wrong motor-rated current is

set to E2-01.

• Check the motor-rated current.
• Enter the value written on the motor nameplate to parameter E2-01.

The motor base frequency for the

drive input power is set too low.

• Check the rated frequency indicated on the motor nameplate.
• Enter the rated frequency to E1-06 (Base Frequency).

Multiple motors are running off the

same drive.

Set L1-01 to 0 to disable the Motor Protection function and install a thermal relay

to each motor.

The electrical thermal protection

characteristics and motor overload

characteristics do not match.

• Check the motor characteristics.
• Correct the value set to L1-01 (Motor Protection Function).
• Install an external thermal relay.

The electrical thermal relay is

operating at the wrong level.

• Check the current rating listed on the motor nameplate.
• Check the value set for the motor-rated current (E2-01).

Motor overheated by

overexcitation operation.

• Overexcitation increases the motor losses and the motor temperature. If applied

too long, motor damage can occur. Prevent excessive overexcitation operation

or apply proper cooling to the motor

• Reduce the excitation deceleration gain (n3-13).
• Set L3-04 (Stall Prevention during Deceleration) to a value other than 4.

Output current fluctuation due to

input phase loss

Check the power supply for phase loss.

Digital Operator Display

Fault Name

oL2

Drive Overload
The thermal sensor of the drive triggered overload protection.

Cause

Possible Solution

Load is too heavy.

Reduce the load.

Cycle times are too short during

acceleration and deceleration.

Increase the settings for the acceleration and deceleration times (C1-01 through

C1-04).

Voltage is too high for the V/f

characteristics.

• Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve

reducing E1-08 and E1-10.

• Be careful not to lower E1-08 and E1-10 excessively because this reduces load

tolerance at low speeds.

Drive capacity is too small.

Replace the drive with a larger model.

Overload occurred when operating

at low speeds.

• Reduce the load when operating at low speeds.
• Replace the drive with a model that is one frame size larger.
• Lower the carrier frequency (C6-02).

Excessive torque compensation.

Reduce the torque compensation gain (C4-01) until there is no speed loss but less

current.

5.4 Fault Detection

136