5 alarm detection, Alarm codes, causes, and possible solutions, Alarm detection – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 141: Refer to alarm

Advertising
background image

5.5

Alarm Detection

Alarms are drive protection functions that do not operate the fault contact. The drive will

return to original status when the cause of the alarm has been removed.
During an alarm condition, the Digital Operator display flashes and an alarm output is

generated at the multi-function output (H2-01), if programmed.
Investigate the cause of the alarm and refer to

Table 5.8

for the appropriate action.

u

Alarm Codes, Causes, and Possible Solutions

Table 5.8 Detailed Alarm Codes, Causes, and Possible Solutions

Digital Operator Display

Minor Fault Name

bb

Baseblock
Drive output interrupted as indicated by an external baseblock signal.

Cause

Possible Solution

Minor Fault

(H2- =

10)

External baseblock signal entered

via multi-function input terminal

(S1 to S5).

Check external sequence and baseblock signal input timing.

No output

Digital Operator Display

Minor Fault Name

CALL

Serial Communication Transmission Error
Communication has not yet been established.

Cause

Possible Solution

Minor Fault

(H2- =

10)

Communications wiring is faulty,

there is a short circuit, or something

is not connected properly.

• Check for wiring errors.
• Correct the wiring.
• Remove and ground shorts and reconnect loose wires.

YES

Programming error on the master

side.

Check communications at start-up and correct programming errors.

Communications circuitry is

damaged.

• Perform a self-diagnostics check.
• Replace the drive if the fault continues to occurs.

Terminal resistance setting is

incorrect.

The terminal slave drive must have the internal terminal resistance

switch set correctly. Place DIP switch S2 to the ON position.

Digital Operator Display

Minor Fault Name

CE

MEMOBUS/Modbus Communication Error
Control data was not received correctly for two seconds.

5.5 Alarm Detection

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

141

5

Troubleshooting

Advertising