A.4 drive specifications – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 207

Advertising
background image

Item

Specification

Environment

Storage/Installation

Area

Indoors

Ambient

Temperature

IP20/NEMA Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F)

IP20/IP00 Open-Chassis enclosure: -10 °C to +50 °C (14 °F to 122 °F)

Finless Type: IP20 enclosure: -10 °C to +50 °C (14 °F to 122 °F)

Humidity

95% RH or less with no condensation

Storage Temperature -20 to +60 °C (-4 to +140 °F) allowed for short-term transport of the

product

Altitude

Up to 1000 meters without derating; up to 3000 meters with output

current and voltage derating.

Shock, Impact

10 to 20 Hz: 9.8 m/s

2

20 to 55 Hz: 5.9 m/s

2

Surrounding Area

Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight

Orientation

Install the drive vertically to maintain maximum cooling effects

Standards

• UL508C
• EN 61800-3:2004/A1:2012, IEC/EN 61800-5-1

Protective Enclosure

IP20/Open-Chassis
IP20/NEMA Type 1

<5>

Cooling Method

BA0001 to BA0006: self-cooled

BA0010: cooling fan

2A0001 to 2A0004: self-cooled

2A0006 to 2A0020: cooling fan

4A0001 to 4A0004: self-cooled

4A0005 to 4A0011: cooling fan

<1>

Instantaneous average deceleration torque refers to the torque required to decelerate the motor (uncoupled from
the load) from the rated motor speed down to zero in the shortest time.

<2>

Ensure that Stall Prevention Selection during Deceleration is disabled (L3-04 = 0) or set to 3 when using a
braking resistor or the Braking Resistor Unit. The default setting for the stall prevention function will interfere
with the braking resistor.

<3>

Overload protection may be triggered when operating with 150% of the rated output current if the output
frequency is less than 6 Hz.

<4>

Ground protection cannot be provided under the following circumstances when a ground fault is likely in the
motor windings during run: Low ground resistance for the motor cable and terminal block; low ground resistance
for the motor cable and terminal block; or the drive is powered up from a ground short.

A.4 Drive Specifications

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

207

A

Specifications