WARNING! Electrical Shock Hazard. Always use a ground wire that complies with technical standards on

electrical equipment and minimize the length of the ground wire. Improper equipment grounding may cause

dangerous electrical potentials on equipment chassis, which could result in death or serious injury.

WARNING! Electrical Shock Hazard. Be sure to ground the drive ground terminal. (200 V Class: Ground to

100 Ω or less, 400 V Class: Ground to 10 Ω or less). Improper equipment grounding could result in death or

serious injury by contacting ungrounded electrical equipment.

NOTICE: Do not share the ground wire with other devices such as welding machines or large-current electrical

equipment. Improper equipment grounding could result in drive or equipment malfunction due to electrical

interference.

NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper

equipment grounding could result in abnormal operation of drive or equipment.

Refer to

Figure 3.9

when using multiple drives. Do not loop the ground wire.

A

B

A – Correct

B – Incorrect

Figure 3.9 Multiple Drive Wiring

3.6 Main Circuit Wiring

50

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide