A.6 drive derating data, Temperature derating, Refer to output current derating due to – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 211: If derating is required. contact a yaskawa sales, Output current derating due to ambient temperature

Advertising
background image

A.6

Drive Derating Data

The drive can be operated at above rated temperature, altitude and default carrier frequency

by derating the drive capacity.

u

Temperature Derating

As the ambient temperature for the drive is increased above the drive specification the drive

should be derated. Additionally parameter L8-35 Installation Method Selection on page

211

should be set according to enclosure type and mounting method as illustrated in

Figure A.1

.

n

Output Current Derating Due to Ambient Temperature

Set L8-12 and L8-35 according to the installation conditions when the ambient temperature

is above the drive specification or if drives are side-by-side mounted in a cabinet. The output

current is derated as shown in

Figure A.1

.

No.

Name

Description

Range

Def.

L8-12

Ambient

Temperature

Setting

Adjust the drive overload (oL2) protection level when the

drive is installed in an environment that exceeds its ambient

temperature rating.

-10 to 50

30 °C

L8-35

Installation

Method

Selection

0: IP20/IP00 Drive

1: Side-by-Side Mounting
2: NEMA Type 1 Drive

<1>

3: Finless Drive or External Heatsink Installation

0 to 3

0

<1>

This selection assumes that the drive is fitted with the NEMA Type 1 Kit option.

40

50

0

30

o

35

50%

70%

80%

85%

100%

o

o

o

Drive

Rating

Ambient tem

p C

Parameter L8-12

Parameter L8-35 = 0 (IP20/IP00 Drive)

Parameter L8-35 = 2
(NEMA Type 1 Drive)

Parameter L8-35 = 1
(Side-by-side Mounting)

Parameter L8-35 = 3
(Finless Drive or External
Heatsink Installation)

Figure A.1 Ambient Temperature and Installation Method Derating