Grounding, Ce standards compliance for dc power supply input – Yaskawa J1000 Compact V/f Control Drive User Manual
Page 246

Table C.1 Factory Recommended Drive Branch Circuit Protection
Drive Model
Fuse Type
Manufacturer: Bussmann
Model
Fuse Ampere Rating (A)
Single-Phase 200 V Class
BA0001
FWH-25A14F
25
BA0002
FWH-25A14F
25
BA0003
FWH-60B
60
BA0006
FWH-80B
80
BA0010
FWH-100B
100
Three-Phase 200 V Class
2A0001
FWH-25A14F
25
2A0002
FWH-25A14F
25
2A0004
FWH-25A14F
25
2A0006
FWH-25A14F
25
2A0010
FWH-70B
70
2A0012
FWH-70B
70
2A0020
FWH-90B
90
Three-Phase 400 V Class
4A0001
FWH-40B
40
4A0002
FWH-40B
40
4A0004
FWH-50B
50
4A0005
FWH-70B
70
4A0007
FWH-70B
70
4A0009
FWH-90B
90
4A0011
FWH-90B
90
n
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the
drive in other types of grounded systems, contact your dealer or Yaskawa for instructions.
n
CE Standards Compliance for DC Power Supply Input
Install the fuses in the following tables to meet CE standards.
C.2 European Standards
246
YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide