Table C.1 Factory Recommended Drive Branch Circuit Protection

Drive Model

Fuse Type

Manufacturer: Bussmann

Model

Fuse Ampere Rating (A)

Single-Phase 200 V Class

BA0001

FWH-25A14F

25

BA0002

FWH-25A14F

25

BA0003

FWH-60B

60

BA0006

FWH-80B

80

BA0010

FWH-100B

100

Three-Phase 200 V Class

2A0001

FWH-25A14F

25

2A0002

FWH-25A14F

25

2A0004

FWH-25A14F

25

2A0006

FWH-25A14F

25

2A0010

FWH-70B

70

2A0012

FWH-70B

70

2A0020

FWH-90B

90

Three-Phase 400 V Class

4A0001

FWH-40B

40

4A0002

FWH-40B

40

4A0004

FWH-50B

50

4A0005

FWH-70B

70

4A0007

FWH-70B

70

4A0009

FWH-90B

90

4A0011

FWH-90B

90

n

Grounding

The drive is designed to be used in T-N (grounded neutral point) networks. If installing the

drive in other types of grounded systems, contact your dealer or Yaskawa for instructions.

n

CE Standards Compliance for DC Power Supply Input

Install the fuses in the following tables to meet CE standards.

C.2 European Standards

246