background image

Cause

Possible Solutions

The

STOP

button was pressed when

the drive was started from a REMOTE

source.

When the

STOP

button is pressed, the drive will decelerate to stop.

• Switch off the run command and then re-enter a run command.

The

STOP

button is disabled when o2-02 is set to 0.

Motor is not producing enough torque.

• Ensure the selected V/f pattern corresponds with the characteristics of

the motor being used.

• Increase both the minimum and mid output frequency voltages (E1-08,

E1-10).

Increase the frequency reference so that it is higher than the minimum

frequency reference (E1-09).
Increase the torque compensation gain (C4-01).

The drive is set for both 2-Wire and

3-Wire sequence at the same time.

• The drive is set for a 3-Wire sequence when one of the parameters H1-03

through H1-05 is set to 0.

• If the drive is supposed to be set up for a 2-Wire sequence, then ensure

parameters H1-03 through H1-05 are not set to 0.

• If the drive is supposed to be set up for a 3-Wire sequence, then H1-

 must be set to 0.

n

Motor Rotates in the Opposite Direction from the Run Command

Cause

Possible Solutions

Phase wiring between the drive and

motor is incorrect.

• Check the motor wiring.
• Switch two motor cables (U, V, and W) to reverse motor direction.
• Connect drive output terminals U/T1, V/T2 and W/T3 in the right order

to the corresponding motor terminals U, V, and W.

• Change the setting of parameter b1-14.

The forward direction for the motor is

setup incorrectly.

Typically, forward is designated as being counterclockwise when looking

from the motor shaft (refer to the figure below).

1

2

1. Forward Rotating Motor (looking down the motor shaft)

2. Motor Shaft

Note:

Check the motor specifications for the forward and reverse directions. The motor specifications will vary

depending on the manufacturer of the motor.

5.8 Troubleshooting without Fault Display