Motor parameters: e2-01 to e2-03, Setting motor parameters – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 104

Advertising
background image

No.

Parameter Name

Setting Range

Default

E1-07

Middle Output Frequency

0.0 to 400.0 Hz

3.0 Hz

E1-08

Middle Output Frequency Voltage

0.0 to 255.0 V

<1>

18.4 V

E1-09

Minimum Output Frequency

0.0 to 400.0 Hz

1.5 Hz

E1-10

Minimum Output Frequency Voltage

0.0 to 255.0 V

<1>

13.8 V

<1>

Values shown here are for 200 V class drives; double the values for 400 V class drives.

E1-05

E1-08

E1-10

E1-09

E1-07 E1-06

E1-04

Output Voltage (V)

Frequency (Hz)

Figure 4.16 V/f Pattern

Note:

1. The following condition must be true when setting up the V/f pattern: E1-09 ≤ E1-07 < E1-06 ≤

E1-04

2. To make the V/f pattern a straight line set E1-09 = E1-07. In this case the E1-08 setting is disregarded.
3. E1-03 is unaffected when the drive is initialized using parameter A1-03, but the settings for E1-04

through E1-10 are returned to their default values.

u

Motor Parameters: E2-01 to E2-03

n

Setting Motor Parameters

The following table provides instructions on how to set motor parameters. Refer to the motor

data sheet for the correct motor data.

No.

Parameter Name

Setting Method

E2-01

Motor Rated Current

Sets the motor nameplate full load current in amperes (A).

E2-02

Motor Rated Slip

Calculate and set the motor rated slip based on the rated speed described on the

motor nameplate.

Motor rated slip = Motor rated frequency [Hz] - Rated speed [r/min] x No. of

motor poles / 120.

4.5 Basic Operation

104

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide