B.2 parameter table – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 231

Advertising
background image

No.

Name

Description

Range Def. Mode Addr.

Hex

Pg.

L4-07

Speed

Agreement

Detection

Selection

0: No detection during baseblock.

1: Detection always enabled.

0, 1

0

O

470

L5: Fault Reset

Use L5 parameters to configure Automatic Restart after fault.

L5-01 Number of

Auto Restart

Attempts

Sets the counter for the number of times the drive

attempts to restart when one of the following faults

occurs: oC, oH1, ov, PF, rH, oL1, oL2, oL3, Uv1.

When the drive operates without fault for 10 minutes,

the counter will be reset.

0 to 10

0

O

49E

L6: Overtorque Detection

Use L6 parameters to configure overtorque detection.

L6-01 Torque

Detection

Selection 1

Selects the overtorque operation. Overtorque is

determined by the settings in parameters L6-02 and

L6-03. The multi-function output settings (H2- 01=

B and 17) are also active if programmed.

0: Disabled

1: oL3 at Speed Agree - Alarm (overtorque detection

only active during Speed Agree and operation

continues after detection).

2: oL3 at RUN - Alarm (overtorque detection is

always active and operation continues after

detection).

3: oL3 at Speed Agree - Fault (overtorque detection

only active during Speed Agree and drive output will

shut down on an oL3 fault).

4: oL3 at RUN - Fault (overtorque detection is always

active and drive output will shut down on an oL3

fault).

0 to 4

0

O

4A1

L6-02 Torque

Detection

Level 1

Sets the overtorque detection level. 100% is equal to

the motor rated current.

0 to 300 150

%

O

4A2

L6-03 Torque

Detection

Time 1

Sets the length of time an overtorque condition must

exist before Torque Detection is triggered.

0.0 to

10.0

0.1 s

O

4A3

L8: Hardware Protection

Use L8 parameters to configure hardware protection functions.

L8-01

Internal

Dynamic

Braking

Resistor

Protection

Selection

(ERF type)

Selects the Braking resistor when using a 3% duty

cycle heatsink mounted braking resistor. This

parameter does not enable or disable the braking

transistor of the drive.

0: Resistor overheat protection disabled

1: Resistor overheat protection enabled

0, 1

0

O

4AD

B.2 Parameter Table

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

231

B

Parameter List

Advertising