Off on, 7 no-load operation test run – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 115

Advertising
background image

Step

Display/Result

3. Press

to give the drive a Run command. RUN will light and

the motor will rotate at 6 Hz.

STOP

Off

On

4. Ensure the motor is rotating in the correct direction and no faults or

alarms occur.

Motor

Forward

5.

If there is no error in step 4, press

to increase the frequency

reference. Increase the frequency in 10 Hz increments verifying

smooth operation results at all speeds. For each frequency, monitor

the drive output current (U1-03) through the LED operator to confirm

the current is well below the motor rated current.

6. The drive should operate normally. Press

STOP

to stop the motor.

RUN flashes until the motor comes to a complete stop.

STOP

Flashing

Off

4.7 No-Load Operation Test Run

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

115

4

Start-Up Programming & Operation