B.2 parameter table – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 221

Advertising
background image

No.

Name

Description

Range Def. Mode Addr.

Hex

Pg.

d3-01 Jump

Frequency 1

d3-01 to d3-04 allow programming of three

prohibited frequency reference points for eliminating

problems with resonant vibration of the motor/

machine. This feature does not eliminate the selected

frequency values, but accelerates and decelerates the

motor through the prohibited bandwidth.

The parameters must be according to the rule

d3-01 ≥ d3-02 .

0.0 to

400.0

0.0

Hz

O

294

d3-02 Jump

Frequency 2

0.0

Hz

O

295

d3-04 Jump

Frequency

Width

This parameter sets the dead-band width around each

selected prohibited frequency reference point. The

bandwidth becomes the designated Jump frequency,

plus or minus d3-04.

0.0 to

20.0

1.0

Hz

O

297

d4: Frequency Reference Hold

Use d4 parameters to configure the drive frequency reference hold function.

d4-01

Frequency

Reference

Hold Function

Selection

Determines if the frequency reference or frequency

reference bias is saved when the Run command is

removed or the power goes off.

0: Disabled

1: Enabled

This parameter is effective when the multi-function

inputs “Accel/Decel Ramp Hold” or “Up/Down”

commands are selected (H1- = A or 10/11).

0, 1

0

O

298

<1>

Parameter can be changed during run.

<2>

Range upper limit is dependent on parameters E1-04, Maximum Output Frequency, and d2-01, Frequency
Reference Upper Limit.

B.2 Parameter Table

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

221