A.4 drive specifications – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 206

Advertising
background image

Item

Specification

Protection

Functions

Motor Protection

Motor overheat protection via output current sensor

Overcurrent

Protection

Drives stops when output exceeds 200% of the rated current (Heavy

Duty)

Overload Protection

A stop command will be entered after operating at 150% for 60 s (Heavy
Duty)

<3>

Overvoltage

Specification

200 V class: Stops when DC bus voltage exceeds approximately 410 V

400 V class: Stops when DC bus voltage exceeds approximately 820 V

Low Voltage

Protection

Drive stops when DC bus voltage falls below the levels indicated:

190 V (3-phase 200 V), 160 V (single-phase 200 V), 380 V (3-phase 400

V), 350 V (3-phase 380 V)

Momentary Power

Loss Ride-Thru

Stops after 15 ms

Heatsink Overheat

Protection

Protected by thermistor

Braking Resistor

Overheat Protection Overheat input signal for braking resistor (Optional ERF-type, 3% ED)

Stall Prevention

During acceleration and during run: Separate settings for each type of

stall prevention determine the current level at which stall prevention is

triggered.

During deceleration: Select, enable/disable.

Cooling Fan Failure

Protection

Circuit protection (“fan-lock” sensor)

Ground Fault

Protection

Electronic circuit protection

<4>

DC Bus Charge LED Remains lit until DC bus voltage falls below 50 V

A.4 Drive Specifications

206

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide