Yaskawa J1000 Compact V/f Control Drive User Manual

Page 91

Advertising
background image

n

Run the Drive using Digital Input Terminals: b1-02 = 1

This setting uses the digital input terminals to enter the run command. The factory setting is

a 2-Wire sequence.
Using a 2-Wire Sequence

Digital Input Terminals

ON

OFF

S1

Forward Run

Stop

S2

Reverse Run

Stop

S1

S2

SC

Drive

Forward Run

Reverse Run

Digital Input Common

Figure 4.9 Example Wiring Diagram for 2-Wire Sequence

Using a 3-Wire Sequence
When H1-05 (Multi-Function Digital Input Terminal S5 Function Selection) = 0, the functions

of terminals S1 and S2 are set to 3-Wire sequence, and the multi-function input terminal

becomes forward/reverse run command terminal.

S1

S2

S5

SC

Run Command

Runs when S1 and S2 are closed

Drive

Stop Button

(N.C.)

Run Button

(N.O.)

Stop Command

Stops when S1 and S2 are open

FWD/REV Command <1>

Digital Input Common

(Run button pushed)

(Stop button pushed)

Figure 4.10 Example Wiring Diagram for 3-Wire Sequence Using Terminal S5

4.5 Basic Operation

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

91

4

Start-Up Programming & Operation