3.2

Standard Connection Diagram

Connect the drive and peripheral devices as shown in

Figure 3.

. It is possible to run the drive

via the digital operator without connecting digital I/O wiring. This section does not discuss

drive operation;

Refer to Start-Up Programming & Operation on page 69

for instructions

on operating the drive.

NOTICE: Inadequate branch short circuit protection could result in damage to the drive. Install adequate

branch circuit short circuit protection per applicable codes. The drive is suitable for circuits capable of

delivering not more than 31,000 RMS symmetrical amperes, 240 Vac maximum (200 V Class) and 480 Vac

maximum (400 V Class).

NOTICE: When the wiring distance is greater than 100 meters, pay special attention to the motor insulation

voltage or use a drive duty motor. Failure to comply could lead to motor insulation breakdown.

NOTICE: Correctly set Sink/Source jumper S3 for internal power supply. Failure to comply may result in

damage to the drive.

Refer to I/O Connections on page 59

for details.

NOTICE: Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause

control circuit malfunction.

NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible

interference related issues. Failure to comply may result in abnormal operation of drive and nearby equipment.

NOTICE: The minimum load for the multi-function relay output MA-MB-MC is 10 mA.

3.2 Standard Connection Diagram

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

39

3

Electrical Installation