Set up the v/f pattern as shown in figure 4.16, 5 basic operation – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 103

Advertising
background image

Table 4.9 Derated Torque Characteristics, Examples E to H

Example E

50 Hz

Example F

50 Hz

Example G

60 Hz

Example H

60 Hz

0

8

200

1.3

25

50

35

V

oltage (V)

Frequency (Hz)

0

9

200

1.3

25

50

50

Voltage (V)

Frequency (Hz)

0

8

200

1.5

30

60

35

Voltage (V)

Frequency (Hz)

0

9

200

1.5

30

60

50

Voltage (V)

Frequency (Hz)

Table 4.10 High Starting Torque, Examples I to L

Example I

50 Hz

Example J

50 Hz

Example K

60 Hz

Example L

60 Hz

0

12

200

1.3 2.5

50

19

Voltage (V)

Frequency (Hz)

0

13

200

1.3 2.5

50

24

Voltage (V)

Frequency (Hz)

0

12

200

1.5 3

60

19

Voltage (V)

Frequency (Hz)

0

15

200

1.5 3

60

24

Voltage (V)

Frequency (Hz)

Table 4.11 Rated Output Operation, Examples M to O

Example M

90 Hz

Example N

120 Hz

Example O

180 Hz

0

12

16

200

1.5 3

90

60

Voltage (V)

Frequency (Hz)

0

12

16

200

1.5 3

120

60

Voltage (V)

Frequency (Hz)

0

12

16

200

1.5 3

180

60

Voltage (V)

Frequency (Hz)

n

V/f Pattern Settings E1-04 to E1-10

Set up the V/f pattern as shown in

Figure 4.16

.

No.

Parameter Name

Setting Range

Default

E1-04

Maximum Output Frequency

40.0 to 400.0 Hz

60 Hz

E1-05

Maximum Voltage

0.0 to 255.0 V

<1>

230 V

E1-06

Base Frequency

0.0 to 400.0 Hz

60 Hz

4.5 Basic Operation

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

103

4

Start-Up Programming & Operation

Advertising