5 basic operation, Current input, Start-up programming & operation – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 89

Advertising
background image

Drive

A1

0 to 10 V

AC

I

V

Main frequency
(voltage or current input)

Analog common

DIP switch S1

Figure 4.7 Voltage Input for the Frequency Reference

Current Input

When entering the frequency reference using an analog input signal, set parameter H3-01 to

“2” if 4 to 20 mA input is used. When using 0 to 20 mA input, set H3-01 to “3”. Set DIP

Switch S1 for current input (position “I”).

V (+10.5 V, 20 mA power supply)

0 or 4 to 20 mA input

DIP switch S1

I

V

Drive

A1

Main Frequency
(current input)

AC

Analog common

Figure 4.8 Current Input for the Frequency Reference

4.5 Basic Operation

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

89

4

Start-Up Programming & Operation