A.2 single/three-phase 200 v class drives, A.2 single/three-phase 200 v class, Drives – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 201

Advertising
background image

A.2

Single/Three-Phase 200 V Class Drives

Table A.2 Power Ratings

Item

Specification

Three-Phase Drive Model

2A0001

2A0002

2A0004

2A0006

2A0010

2A0012

2A0020

Single-Phase Drive Model

<1>

BA0001

BA0002

BA0003

BA0006

BA0010

-

-

Maximum Motor Size Allowed

(HP)

<2>

ND Rating

0.125

& 0.25

0.25

0.5

& 0.75

1.0 &

1.5

2.0 &

3.0

3.0

5.0

HD Rating

0.125

0.25

0.5

0.75 & 1

2.0

3.0

5.0

Input

Input

Current (A)

<3>

Three-

Phase

ND Rating

1.1

1.9

3.9

7.3

10.8

13.9

24.0

HD Rating

0.7

1.5

2.9

5.8

7.5

11.0

18.9

Single-

Phase

ND Rating

2.0

3.6

7.3

13.8

20.2

-

HD Rating

1.4

2.8

5.5

11.0

14.1

-

-

Output

Rated Output Capacity

(kVA)

<4>

ND Rating

0.5

0.7

1.3

2.3

3.7

4.6

7.5

HD Rating

0.3

0.6

1.1

1.9

3.0

4.2

6.7

Output Current (A)

ND Rating

<5>

1.2

1.9

3.5

(3.3)

6.0

9.6

12.0

19.6

HD Rating 0.8

<6>

1.6

<6>

3.0

<6>

5.0

<6>

8.0

<7>

11.0

<7>

17.5

<7>

Overload Tolerance

ND Rating: 120% of rated output current for 1 minute

HD Rating: 150% of rated output current for 1 minute

(Derating may be required for applications that start and stop

frequently)

Carrier Frequency

2 kHz (user-set, 2 to 15 kHz)

Max Output Voltage (V)

Three-phase power: 200 to 240 V

Single-phase power: 200 to 240 V

(both proportional to input voltage)

Max Output Frequency (Hz)

400 Hz (user-adjustable)

Power

Supply

Rated Voltage

Rated Frequency

Three-phase power: 200 to 240 V 50/60 Hz

Single-phase power: 200 to 240 V 50/60 Hz

DC power supply: 270 to 340 V

<8>

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency Fluctuation

±5%

Harmonic Corrective

Actions

DC Link Choke

Optional

<1>

Drives with a single-phase power supply input will output three-phase power and cannot run a single-phase
motor.

<2>

Horsepower rating is based on 230 V Induction-Type Squirrel Cage NEMA B 4-Pole Motors as represented in
NEC Table 430.250 Full-Load Current, Three-Phase Alternating-Current Motors.

<3>

Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and
power supply impedance.

A.2 Single/Three-Phase 200 V Class Drives

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

201

A

Specifications

Advertising