8 troubleshooting without fault display, Cannot change parameter settings, Troubleshooting without fault display – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 151

Advertising
background image

5.8

Troubleshooting without Fault Display

This section describes troubleshooting problems that do not trip an alarm or fault.

u

Cannot Change Parameter Settings

Cause

Possible Solutions

The drive is running the motor (i.e., the

Run command is present).

• Stop the drive and switch over to the Programming Mode.
• Most parameters cannot be edited during run.

The Access Level is set to restrict access

to parameter settings.

• Set the Access Level to allow parameters to be edited (A1-01 = 2).

The operator is not in the Parameter Setup

Mode (the LED screen will display

“PAr”).

• See what mode the LED parameter is current set for.
• Parameters cannot be edited when in the Setup Mode (“STUP”). Switch

modes so that “PAr” appears on the screen.

The wrong password was entered.

• If the password entered to A1-04 does not match the password saved to

A1-05, then drive settings cannot be changed.

• Reset the password.
If you cannot remember the password:

Display parameter A1-04. Press the

STOP

button while pressing

at the same time. Parameter A1-05 will appear.

• Set a new password to parameter A1-05.

Undervoltage was detected.

• Check the drive input power voltage by looking at the DC bus voltage

(U1-07).

• Check all main circuit wiring.

5.8 Troubleshooting without Fault Display

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

151

5

Troubleshooting

Advertising