Wiring procedure, Table 3.9, For ferrule terminal types and sizes – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 56

Advertising
background image

Table 3.9 Ferrule Terminal Types and Sizes

Size mm

2

(AWG)

Type

L (mm)

d1 (mm)

d2 (mm)

Manufacturer

0.25 (24)

AI 0.25-6YE

10.5

0.8

2.0

PHOENIX CONTACT

0.34 (22)

AI 0.34-6TQ

10.5

0.8

2.0

0.5 (20)

AI 0.5-6WH

12

1.1

2.5

0.75 (18)

AI 0.75-6GY

12

1.3

2.8

1.0

AI 1-6RD

12

1.5

3.0

u

Wiring Procedure

This section describes the proper procedures and preparations for wiring the control terminals.

WARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on.

Failure to comply could result in death or serious injury.

NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1,

V/T2, W/T3, -, +1, +2) and other high-power lines. Improper wiring practices could result in drive malfunction

due to electrical interference.

NOTICE: Separate wiring for digital output terminals MA, MB and MC from wiring to other control circuit lines.

Improper wiring practices could result in drive or equipment malfunction or nuisance trips.

NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper

application of peripheral devices could result in drive performance degradation due to improper power supply.

NOTICE: Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment.

Improper wiring practices could result in drive or equipment malfunction due to short circuit.

NOTICE: Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment

grounding could result in drive or equipment malfunction or nuisance trips.

Wire the control terminals using

Figure 3.13

as a guide. Prepare the ends of the control circuit

wiring as shown in

Figure 3.14

.

Refer to Wire Size and Torque Specifications on page 55

.

NOTICE: Do not tighten screws beyond the specified tightening torque. Failure to comply may damage the

terminal.

NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices

could result in drive or equipment malfunction due to electrical interference.

Connect control wires as shown in the following figure:

3.7 Control Circuit Wiring

56

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide