Transistor input signal using 0 v common/sink mode, 8 i/o connections – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 60

Advertising
background image

n

Transistor Input Signal Using 0 V Common/Sink Mode

When controlling the digital inputs by NPN transistors (0 V common/sinking mode), set the

DIP switch S3 to SINK and use the internal 24 V power supply.

S1

SINK

SOURCE

S2

S3

S3

+24 V

S4

S5

SC

SINK

SOURCE

FWD Run/Stop

REV Run/Stop

External Fault N.O.

Fault Reset

Multi-step Speed 1

Shielded Cable

Multi-funciton input

Figure 3.17 Sinking Mode: Sequence from NPN Transistor (0 V Common)

3.8 I/O Connections

60

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide