Table C.11 Factory Recommended Drive Branch Circuit Protection

Drive

Model

Non-time

Delay

Fuse Rating

(A)

<1>

Time Delay Fuses

Bussmann

Semiconductor

Fuse Part Number

(Fuse Ampere)

<4>

MCCB

<5>

Class J, T,

or CC

Fuse Rating

(A)

<2>

Class RK5

Fuse Rating

(A)

<3>

Rating (A)

Minimum

Enclosure

Volume (in

3

)

200 V Class Single-Phase Drives

BA0001

6

3.5

4

FWH-25A14F (25)

15

600

BA0002

10

6

8

FWH-25A14F (25)

15

600

BA0003

20

10

15

FWH-60B (60)

15

600

BA0006

40

20

30

FWH-80B (80)

30

1152

BA0010

40

35

45

FWH-100B (100)

50

1152

200 V Class Three-Phase Drives

2A0001

3

1.5

2

FWH-25A14F (25)

15

600

2A0002

6

<6>

3

3

FWH-25A14F (25)

15

600

2A0004

15

<7>

6

8

FWH-25A14F (25)

15

600

2A0006

20

10

15

FWH-25A14F (25)

15

1152

2A0010

25

15

20

FWH-70B (70)

25

1152

2A0012

25

20

30

FWH-70B (70)

30

1152

2A0020

40

40

50

FWH-90B (90)

60

1152

400 V Class Three-Phase Drives

4A0001

3

2

2

FWH-40B (40)

15

1152

4A0002

6

3.5

3

FWH-40B (40)

15

1152

4A0004

15

<7>

7

8

FWH-50B (50)

15

1152

4A0005

20

<8>

10

10

FWH-70B (70)

15

1152

4A0007

25

<9>

12

15

FWH-70B (70)

20

1152

4A0009

25

15

20

FWH-90B (90)

20

1152

4A0011

30

20

30

FWH-90B (90)

35

1152

<1>

Maximum 300% of drive input current rating for any Class J, T, or CC fuse except for models 2A0002, 2A0004,
4A0004, 4A0005, and 4A0007.

<2>

Maximum 175% of drive input current rating for any Class J, T, or CC fuse.

<3>

Maximum 225% of drive input current rating for any Class RK5 fuse.

<4>

When using semiconductor fuses, Bussmann FWH are required for UL compliance.

<5>

Maximum MCCB Rating is 15 A or 200% of drive input current rating, whichever is larger. MCCB voltage
rating must be 600 Vac or greater. Additionally, when using MCCBs for protection, the drive must be installed
in a ventilated enclosure with minimum volume according the “Minimum Enclosure Volume” column.

<6>

Model 2A0002 requires Mersen (Ferraz) part number A6T6 for compliance.

<7>

Models 2A0004 and 4A0004 require Mersen (Ferraz) part number A6T15 for compliance.