u

L: Protection Function

L parameters provide protection to the drive and motor, such as: control during momentary

power loss, Stall Prevention, frequency detection, fault restarts, overtorque detection, and

other types of hardware protection.

No.

Name

Description

Range Def. Mode Addr.

Hex

Pg.

L1: Motor Protection Functions

Use L1 parameters to configure motor protective functions.

L1-01

Motor

Overload

Protection

Selection

Sets the motor thermal overload protection (oL1)

based on the cooling capacity of the motor.

0: Disabled

1: General Purpose Motor (Standard Fan-Cooled)

2: Drive Dedicated Motor with a Speed Range of 1:10

NOTICE: When multiple motors are used the drive

may not be able to provide protection, even if it is

enabled in L1-01. Set L1-01 to “0” and ensure each

motor has a thermal relay installed.

0 to 2

1

S

480

107

L1-02

Motor

Overload

Protection

Time

Sets the motor thermal overload protection (oL1)

time.

A larger L1-02 time will increase the time for an oL1

fault to occur.

This parameter does not typically require adjustment.

Should be set in accordance with the overload

tolerance of the motor.

0.1 to

20.0

8.0

min

O

481

107

L1-13

Continuous
Electrothermal
Operation
Selection

Determines whether or not to hold the electrothermal

value when the power supply is interrupted.

0: Disabled

1: Enabled

0, 1

1

O

46D

L2: Momentary Power Loss

Use L2 parameters to configure drive functions for momentary power loss conditions.

L2-01

Momentary

Power Loss

Operation

Selection

Enables and disables the momentary power loss

function.

0: Disabled - Drive trips on (Uv1) fault when power

is lost.

1: Power Loss Ride-Thru Time - Drive will restart if

power returns within the Power Loss Ride-Thru

Time.

2: CPU Power Active - Drive will restart if power

returns as long as the CPU is working.

0 to 2

0

O

485

L3: Stall Prevention Function

Use L3 parameters to configure the Stall Prevention function.

B.2 Parameter Table

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

229

B

Parameter List