Digital Operator Display

Fault Name

The following two functions are set

at the same time:
• Up/Down Command (10 vs.

11)

• Hold Accel/Decel Stop (A)

• Check if contradictory settings have been assigned to the multi-function input

terminals at the same time.

• Correct setting errors.

One of the following settings is set

at the multi-function input

terminals:
• External Search Command 1

and External Search Command

2 (61 vs. 62)

• Fast-Stop N.O. and Fast-Stop

N.C. (15 vs. 17)

Digital Operator Display

Fault Name

oPE05

Run Command/Frequency Reference Source Selection Error

Cause

Possible Solution

Frequency reference is assigned to

an option unit (b1-01 = 2 or 3) that

is not connected to the drive.

Reconnect the option card to the drive.

The Run command is assigned to

serial communication (b1-02 = 2)

but no communication option is

connected to the drive.

Digital Operator Display

Fault Name

oPE10

V/f Data Setting Error
One or more of the parameters listed below are not set according to the formula:

E1-09 ≤ E1-07 < E1-06 ≤ E1-04

Cause

Possible Solution

Digital Operator Display

Fault Name

oPE11

Carrier Frequency Setting Error
Correct the setting for the carrier frequency.

Cause

Possible Solution

The following simultaneous

contradictory settings: C6-05 is

greater than 6 and C6-04 is greater

than C6-03 (carrier frequency

lower limit is greater than the upper

limit). If C6-05 is less than or equal

to 6, the drive operates at C6-03.

Correct the parameter settings.

Upper and lower limits between

C6-02 and C6-05 contradict each

other.

5.6 Operator Programming Errors

148