J1000 – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 40

Advertising
background image

SA

Motor

Cooling fan

Forward run/stop

Reverse run/stop

External fault

Fault reset

0 to +10 Vdc
(2 mA)

DIP
switch S3

DC link choke
(option)

Digital inputs
(default setting)

Fault

J1000

Shield ground

terminal

Thermal relay

(option)

Braking resistor

(option)

Main circuit

Control circuit

Thermal relay for

motor cooling fan

Fault relay

1 MCCB

MC

2 MCCB

r1

s1

t1

R/L1

S/L2

T/L3

S1

S2

S3

S4

S5

<3>

<1>

<2>

-

B1

+1

+2

B2

R/L1

S/L2

T/L3

MC

THRX

TRX

MC

TRX

MC MA

U/T1

V/T2

W/T3

24

V

MA

MB

MC

I

V

+24

V 8

mA

M

M

r1

s1

t1

FU

FV
FW

U

V

W

SC

AM

AC

+

-

AM

+V

A1

AC

2 k

Ground
10 or less (400 V class)
100 or less (200 V class)

Setting power supply
+10.5 max. 20 mA

For single phase 200 V

power supply, use

R/L1 and S/L2.

Analog monitor
output

Digital output
250 Vac, 10 mA to 1 A
30 Vdc, 10 mA to 1 A
(default setting)

Main speed
frequency
reference.
Multi-function
programmable

Multi-step
speed 1
main/aux switch

2 MCCB THRX

OFF ON MC

SA

SA

Three phase

power supply

for 200 V /400 V

Jumper

DIP switch S1

Sink

Source

Terminals +1, +2, , B1, and B2

are for connecting options.

Never connect power supply

lines to these terminals.

_

Monitor
output

Option unit

connector

main circuit terminal

shielded line

twisted-pair shielded line

control terminal

<4>

<5>

<6>

<7>

0 to +10 V (20 k )

(0)4 to 20 mA (250 )

Figure 3.1 Drive Standard Connection Diagram (200 V Class Example)

<1>

Remove the jumper when installing an optional DC link choke.

<2>

The MC on the input side of the main circuit should open when the thermal relay is

triggered.

<3>

Self-cooled motors do not require separate cooling fan motor wiring.

<4>

Connected using sequence input signal (S1 to S5) from NPN transistor; Default: sink

mode (0 V com).

<5>

Use only a +24 V internal power supply in sinking mode; the source mode requires

an external power supply.

Refer to I/O Connections on page 59

.

<6>

Minimum load: 5 Vdc, 10 mA (reference value).

3.2 Standard Connection Diagram

40

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide