B.2 parameter table – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 234

Advertising
background image

No.

Name

Description

Range Def. Mode Addr.

Hex

Pg.

o2-04 Drive Model

Selection

Sets the drive model.

This parameter only needs to be set when installing a

new control board. Do not change for other reason.

0 to FF

dep.

on

drive

spec.

O

508

o2-05

Frequency

Reference

Setting

Method

Selection

Selects if the ENTER key must be pressed when

inputting the frequency reference by the operator

keypad.

0: Data/Enter key must be pressed to enter a frequency

reference.

1: Data/Enter key is not required.

The output frequency changes immediately when the

reference is changed by the UP or DOWN keys on the

digital operator. The ENTER key does not need to be

pressed.

Note: When o2-05 is set to 1, the power supply to the

drive must remain on for at least 5 seconds after

making changes to the frequency reference.

0, 1

0

O

509

o2-06

Operation

Selection

when Digital

Operator is

Disconnected

Sets drive action when the digital operator is removed

in LOCAL mode or with b1-02 = 0 (valid for optional

remote operator only).

0: The drive will continue operation

1: The drive will trigger a fault (oPr) and the motor

will coast to stop

0, 1

0

O

50A

o2-09

Factory use.

o3: Copy Function

Use o3 parameters to Read, Copy and Verify the parameter settings to and from the drive.

o3-01

Copy

Function

Selection

0: Copy select

1: INV → OP READ (Read parameters from the

drive, saving them onto the digital operator.)

2: OP → INV WRITE (Copy parameters from the

digital operator, writing them to the drive.)

3: OP → INV VERIFY (Verify parameter settings on

the drive to check if they match the data saved on the

operator.)

To read the drive parameter settings into the digital

operator, set o3-02 to 1 (to allow reading).

0 to 3

0

O

515

o3-02

Copy

Allowed

Selection

Locks the READ operation to prevent accidental

overwriting of the data stored in the LED operator.

0: READ operation prohibited

1: READ operation allowed

0, 1

0

O

516

o4: Maintenance Period

Use o4 parameters to perform maintenance.

o4-01 Accumulated

Operation

Time Setting

Sets the value for the cumulative operation time of the

drive in units of 10 h.

0 to

9999

0

O

50B

o4-02

Accumulated

Operation

Time

Selection

Determines, how the cumulative operation time

(U4-01) is counted.

0: Logs power-on time

1: Logs operation time when the drive output is active

(output operation time).

0, 1

0

O

50C

B.2 Parameter Table

234