Wire Size and Torque Specifications

Select appropriate wire type and size from

Table 3.8

. For simpler and more reliable wiring,

crimp ferrules to the wire ends. Refer to

Table 3.9

for ferrule terminal types and sizes.

Table 3.8 Wire Size and Torque Specifications (Same for All Models)

Terminal Screw

Size

Tightenin

g Torque

N•m

Tightenin

g Torque

(in-lbs)

Bare Wire Terminal

Ferrule-Type Terminal

Applic.

wire size

mm

2

(AWG)

Recomm.

mm

2

(AWG)

Applic.

wire size

mm

2

(AWG)

Recomm.

mm

2

(AWG)

Wire

Type

MA, MB,

MC

M3

0.5 to 0.6

4.4 to 5.3

Stranded:

0.25 to 1.5

(24 to 16)

Single: 0.25

to 1.5

(24 to 16)

0.75 (18)

0.25 to 1.0

(24 to 17)

0.5 (20)

Shielded

line, etc.

S1-S5,

SC, +V,

A1, AC,

AM

M2

0.22 to 0.25

1.9 to 2.2

Stranded:

0.25 to 1.0

(24 to 18)

Single: 0.25

to 1.5

(24 to 16)

0.75 (18)

0.25 to 0.5

(24 to 20)

0.5 (20)

n

Ferrule-Type Wire Terminations

Crimp a ferrule to signal wiring to improve wiring simplicity and reliability. Use CRIMPFOX

6, a crimping tool manufactured by PHOENIX CONTACT.

d1

d2

6 mm

L

Figure 3.12 Ferrule Dimensions

3.7 Control Circuit Wiring

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

55

3

Electrical Installation

Advertising