2 mechanical installation, Installation environment, Mechanical installation – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 29

Advertising
background image

2.2

Mechanical Installation

This section outlines specifications, procedures, and environment for proper mechanical

installation of the drive.

u

Installation Environment

To help prolong the optimum performance life of the drive, install the drive in the proper

environment. The table below provides a description of the appropriate environment for the

drive.

Table 2.1 Installation Environment

Environment

Conditions

Installation Area

Indoors

Ambient

Temperature

IP20/NEMA Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F)

IP20/IP00 Open-Chassis enclosure: -10 °C to +50 °C (14 °F to 122 °F)

Finless Type: IP20 enclosure: -10 °C to +50 °C (14 °F to 122 °F)

Drive reliability improves in environments without wide temperature fluctuations.

When using an enclosure panel, install a cooling fan or air conditioner in the area to ensure

that the air temperature inside the enclosure does not exceed the specified levels.

Do not allow ice to develop on the drive.

Humidity

95% RH or less and free of condensation

Storage Temperature -20 °C to +60 °C (-4 °F to +104 °F)

Surrounding Area

Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight

Altitude

Up to 1000 meters without derating; up to 3000 meters with output current, ambient

temperature, and voltage derating.

Vibration

10 to 20 Hz at 9.8 m/s

2

20 to 55 Hz at 5.9 m/s

2

Orientation

Install the drive vertically to maintain maximum cooling effects.

NOTICE: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during

installation and project construction. Failure to comply could result in damage to the drive. Place a temporary

cover over the top of the drive during installation. Remove the temporary cover before startup, as the cover

will reduce ventilation and cause the drive to overheat.

NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive. Failure to

comply could result in erroneous operation. If such devices must be used in close proximity to the drive, take

proper steps to shield the drive from noise.

2.2 Mechanical Installation