12 wiring checklist – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 67

Advertising
background image

3.12 Wiring Checklist

No.

Item

Page

Drive, peripherals, option cards

1

Check drive model number to ensure receipt of correct model.

19

2

Check for correct braking resistors, DC link chokes, noise filters, and other peripheral

devices.

64

Installation area and physical setup

3

Ensure area surrounding the drive complies with specifications.

29

Power supply voltage, output voltage

4

The voltage from the power supply should fall within the input voltage specification range

of the drive.

5

The voltage rating for the motor should match the drive output specifications.

19

Main circuit wiring

6

Confirm proper branch circuit protection exists per National and Local codes.

39

7

Properly wire the power supply to drive terminals R/L1, S/L2 and T/L3.

42

8

Properly wire the drive and motor together. The motor lines and drive output terminals

R/T1, V/T2 and W/T3 should match in order to produce the desired phase order. If the

phase order is incorrect, the drive will rotate in the opposite direction.

49

9

Use 600 Vac vinyl-sheathed wire for the power supply and motor lines.

46

10

Use the correct wire gauges for the main circuit. Refer to

Table 3.2

through

Table 3.4

.

46

• When using comparatively long motor cable, calculate the amount of voltage drop.

3 x voltage resistance (Ω/km) x cable length (m) x motor rated current (A) x 10

-3

Motor rated voltage (V) x 0.02 ≥

46

• If the cable between the drive and motor exceeds 50 m, adjust the carrier frequency

(C6-02) accordingly.

49

11

Properly ground the drive. Review page

49

.

49

12

Tightly fasten all terminal screws (control circuit terminals, grounding terminals). Refer

to

Table 3.2

through

Table 3.4

..

46

3.12 Wiring Checklist

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

67

3

Electrical Installation

Advertising