D: references, B.2 parameter table – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 220

Advertising
background image

u

d: References

Reference parameters are used to set the various frequency reference values during operation.

No.

Name

Description

Range Def. Mode Addr.

Hex

Pg.

d1: Frequency Reference

Use d1 parameters to configure the drive frequency reference.

d1-01

<1>

Frequency

Reference 1

Frequency reference.

Refer to Frequency Reference

Source: b1-01 on page 88

for instructions to use

d1-01 as the main frequency reference.

0.00 to

400.00

Hz

<2>

0.00

Hz

S

280

97

d1-02

<1>

Frequency

Reference 2

Frequency reference when digital input "Multi-Step

Speed Reference 1" (H1- = 3) is on.

0.00

Hz

S

281

97

d1-03

<1>

Frequency

Reference 3

Frequency reference when digital input "Multi-Step

Speed Reference 2” (H1- = 4) is on.

0.00

Hz

S

282

97

d1-04

<1>

Frequency

Reference 4

Frequency reference when digital inputs "Multi-Step

Speed Reference 1, 2" (H1- = 3 and 4) are on.

0.00

Hz

S

283

97

d1-05

<1>

Frequency

Reference 5

Frequency reference when digital input "Multi-Step

Speed Reference 3" (H1- = 5) is on.

0.00

Hz

O

284

d1-06

<1>

Frequency

Reference 6

Frequency reference when digital inputs "Multi-Step

Speed Reference 1, 3 " (H1- = 3 and 5) are on.

0.00

Hz

O

285

d1-07

<1>

Frequency

Reference 7

Frequency reference when digital inputs "Multi-Step

Speed Reference 2, 3" (H1- = 4 and 5) are on.

0.00

Hz

O

286

d1-08

<1>

Frequency

Reference 8

Frequency reference when multi-function input

"Multi-Step speed reference 1, 2, 3" (H1- = 3, 4,

5) are on.

0.00

Hz

O

287

d1-17

<1>

Jog Frequency

Reference

Frequency reference when digital inputs "Jog

Frequency Reference", "Forward Jog" or "Reverse

Jog." are on.

6.00

Hz

S

292

d2: Frequency Upper and Lower Limits

Use d2 parameters to configure the frequency reference limits.

d2-01 Frequency

Reference

Upper Limit

Sets the frequency reference upper limit as a

percentage of maximum output frequency (E1-04).

Output speed is limited to this value even if the

frequency reference is higher. This limit applies to all

frequency reference sources.

0.0 to

110.0

100.

0%

O

289

d2-02 Frequency

Reference

Lower Limit

Sets the frequency reference lower limit as a

percentage of maximum output frequency (E1-04).

Output speed is limited to this value even if the

frequency reference is lower. This limit applies to all

frequency reference sources.

0.0 to

110.0

0.0%

O

28A

d3: Jump Frequency

Use d3 parameters to configure the drive Jump Frequency settings.

B.2 Parameter Table