Main Frequency Reference

u

DIP Switch S1 Analog Input Signal Selection

The main frequency reference can either be a voltage or current signal input at terminal A1.
When using input A1 as a voltage input, set DIP switch S1 to “V” (right position, default

setting) and program parameter H3-01 to “0” (0 to +10 Vdc with lower limit) or “1” (0 to +10

Vdc without lower limit).
To use current input at terminal A1, set the DIP switch S1 to "I" and set parameter H3-01 =

“2” or “3” (4-20 mA or 0-20 mA).

Table 3.11 Frequency Reference Configurations

Voltage Input

Current Input

+10.5 V
20 mA current

Main speed frequency
reference (voltage input)

Frequency reference
common

Drive

+V

A1

AC

0 to 10 V

+10.5 V
20 mA current

Main speed
frequency reference
(current input)

Frequency
reference
common

+V

A1

AC

Drive

4 to 20 mA input
or
0 to 20 mA input

I

V

DIP Switch S1

Figure 3.19 DIP Switch S1

3.9 Main Frequency Reference

62