C2-01

S-Curve

Characteristic

at Accel Start

The S-curve can be controlled in the four points

shown below.

Run

command

Output

frequency

Time

C2-01

C2-04

C2-02

C2-03

ON

OFF

S-curve is used to further soften the starting and

stopping ramp. The longer the S-curve time, the

softer the starting and stopping ramp.

0.00 to

10.00

0.20

s

O

20B

C2-02

S-Curve

Characteristic

at Accel End

0.00 to

10.00

0.20

s

O

20C

C2-03

S-Curve

Characteristic

at Decel Start

0.00 to

10.00

0.20

s

O

20D

C2-04

S-Curve

Characteristic

at Decel End

0.00 to

10.00

0.00

s

O

20E

C3: Slip Compensation

Use C3 parameters to configure the slip compensation function.

C3-01

<1>

Slip
Compensation
Gain

Sets the slip compensation gain. Decides for what

amount the output frequency is boosted in order to

compensate the slip.

Note: Adjustment is not normally required.

0.0 to

2.5

0.0

O

20F

C3-02

Slip
Compensation
Primary Delay
Time

Adjusts the slip compensation function delay time.

Decrease the setting when the slip compensation

response is too slow, increase it when the speed is

not stable.

0 to

10000

2000

ms

O

210

C4: Torque Compensation

Use C4 parameters to configure Torque Compensation function.

C4-01

<1>

Torque
Compensation
Gain

Sets the gain for the automatic torque (voltage) boost

function and helps to produce better starting torque.

Increase this setting when using a long motor cable

or when the motor is significantly smaller than the

drive capacity.

Decrease this setting when motor oscillation occurs.

Set the value so that the current at low speed does not

exceeds the drive rated current.

0.00 to

2.50

1.00

O

215

C6: Carrier Frequency

Use C6 parameters to configure the carrier frequency drive settings.

C6-01 Drive Duty

Selection

Selects the load rating for the drive.

0: Heavy Duty (HD) for constant torque applications.

1: Normal Duty (ND) for variable torque

applications.

This setting affects the Rated output current and

overload tolerance of the drive.

0, 1

1

S

223

95

B.2 Parameter Table

218