Alarm outputs for maintenance monitors – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 169

Advertising
background image

Table 6.4 Performance Life Monitors Used for Component Replacement

Parameter

Component

Contents

U4-04

Cooling Fan

Displays the accumulated cooling fan operation time as a percentage of the

specified maintenance period (displayed in percent %).

U4-05

Main Circuit (DC bus)

Electrolytic Capacitors

Displays the accumulated time the capacitors are used as a percentage of the

specified maintenance period.

U4-06

Inrush (pre-charge)

relay

Displays the number of times the drive is powered up as a percentage of the

performance life of the inrush circuit.

U4-07

IGBT

Displays the percentage of the maintenance period reached by the IGBTs.

n

Alarm Outputs for Maintenance Monitors

An output can be set up to inform the user when a specific components has neared its expected

performance life.
When one of multi-function digital output terminals has been assigned the maintenance

monitor function (H2- = 2F), the terminal will close when the cooling fan, DC bus

capacitors, or DC bus pre-charge relay reach 90% of the expected performance life, or when

the IGBTs have reached 50% of their expected performance life. Additionally the digital

operator will display an alarm like shown in

Table 6.5

to indicate the specific components

that may need maintenance.

Table 6.5 Maintenance Alarms

Digital Operator Alarm

Display

Function

Corrective Action

<1>

LT-1

The cooling fans have reached 90% of their

designated life time.

Replace the cooling fan.

<1>

LT-2

The DC bus capacitors have reached 90%

of their designated life time.

Contact a Yaskawa

representative or the nearest

Yaskawa sales office on

possible drive replacement.

<1>

LT-3

The DC bus charge circuit has reached

90% of its designated life time.

Contact a Yaskawa

representative or the nearest

Yaskawa sales office on

possible drive replacement.

<1>

LT-4

The IGBTs have reached 50% of their

designated life time.

Check the load, carrier

frequency, and output

frequency.

<2>

TrPC

The IGBTs have reached 90% of their

designated life time.

Contact a Yaskawa

representative or the nearest

Yaskawa sales office on

possible drive replacement.

<1>

This alarm message will be output only if the Maintenance Monitor function is assigned to one of the digital
outputs (H2- = 2F). The alarm will also trigger a digital output that is programmed for alarm indication (H2-
 = 10).

6.3 Periodic Maintenance

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

169

6

Periodic Inspection & Maintenance