20 (2) related parameters – Yaskawa Sigma-5 User Manual: Design and Maintenance - Rotary Motors - MECHATROLINK-II Communications Reference User Manual

Page 105

Advertising
background image

4 Operation

4.3.7 SEMI F47 Function (Torque Limit Function for Low DC Power Supply Voltage for Main Circuit)

4-20

(2) Related Parameters

∗ The setting unit is a percentage of the rated torque.

Note: When using SEMI F47 function, set 1000 ms.

Parameter

Meaning

When Enabled Classification

Pn008

n.

0

[Factory setting]

Does not detect undervoltage.

After restart

Setup

n.

1

Detects warning and limits torque by host controller.

n.

2

Detects warning and limits torque by Pn424 and Pn425.
(Only in the SERVOPACK)

Torque Limit at Main Circuit Voltage Drop

Classification

Pn424

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 100

1%*

50

Immediately

Setup

Release Time for Torque Limit at Main Circuit

Voltage Drop

Classification

Pn425

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 1000

1 ms

100

Immediately

Setup

Pn509

Instantaneous Power Cut Hold Time

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

20 to 1000

1 ms

20

Immediately

Setup

Speed

Position

Torque

Speed

Position

Torque

Speed

Position

Torque

Advertising