7 multiturn limit disagreement alarm (a.cc0) – Yaskawa Sigma-5 User Manual: Design and Maintenance - Rotary Motors - MECHATROLINK-II Communications Reference User Manual

Page 133

Advertising
background image

4 Operation

4.7.7 Multiturn Limit Disagreement Alarm (A.CC0)

4-48

Set the value, the desired rotational amount -1, to Pn205.

Note: The standard specification of the direct drive motor include an absolute encoder that shows values for a single rota-

tion, so the multiturn data (rotational serial data) for the encoder is always 0. The absolute value of the load side can
be created with the motor shaft angle only even when constructing an absolute position detecting system because the

servomotor and the load can be directly connected.

4.7.7 Multiturn Limit Disagreement Alarm (A.CC0)

When the multiturn limit set value is changed with parameter Pn205, a multiturn limit disagreement alarm

(A.CC0) will be displayed because the value differs from that of the encoder.

If this alarm is displayed, perform the operation described below and change the multiturn limit value in the

encoder to the value set in Pn205.

This setting can be performed with the adjustment command (ADJ).

For information the adjustment command (ADJ), refer to

Σ

-V Series User’s Manual MECHATROLINK-II

Commands (No.: SIEP S800000 54).

Factory Setting (= 65535)

Other Setting (

≠65535)

+32767

-32768

Motor rotations

0

Rotational
data

Reverse

Forward

0

Motor rotations

Pn205 setting value

Reverse

Forward

Rotational
data

Alarm

Display

Alarm Name

Alarm Output

Meaning

A.CC0

Multiturn Limit Disagreement

OFF (H)

Different multiturn limits have been set in the
encoder and SERVOPACK.

Step

Display after Operation

Keys

Operation

1

Press the

Key to select the utility function. And

press the

or

Key to select the Fn013.

2

Press the

Key to view the execution display of

Fn013.

Note: If the display is not switched and “NO-OP” is

displayed in the status display, the Write Pro-

hibited Setting (Fn010 = 0001) is set. Check

the setting and reset.

3

Press the

Key to set the multiturn limit value.

When the setting is completed, the status display

shows "DONE" for one second. The status display

then returns to show "A.CC0" again.
Note: If the

Key is pressed instead of the

Key, the multiturn limit value will not be reset.

4

Press the

Key to return to the display the proce-

dure 1.

5

To enable the change in the setting, turn the power OFF and ON again.

A . C C 0
F n 0 1 2 : S o f t V e r
F n 0 1 3 : M t u r n L m S e t
F n 0 1 4 : O p t I n i t
F n 0 1 B : V i b l v l I n i t

- F U N C T I O N -

A . C C 0
ޓ M u l t i t u r n L i m i t
ޓ ޓ ޓ   S e t
ޓ ޓ S t a r t : [ D A T A ]
ޓ ޓ R e t u r n : [ S E T ]

A . C C 0
M u l t i t u r n L i m i t
S e t
S t a r t : [ D A T A ]
R e t u r n : [ S E T ]

A . C C 0
F n 0 1 2 : S o f t V e r
F n 0 1 3 : M t u r n L m S e t
F n 0 1 4 : O p t I n i t
F n 0 1 B : V i b l v l I n i t

- F U N C T I O N -