5) power supply capacities and power losses – Yaskawa Sigma-5 User Manual: Design and Maintenance - Rotary Motors - MECHATROLINK-II Communications Reference User Manual

Page 62

Advertising
background image

3.1 Main Circuit Wiring

3-13

3

Wi

ring and

C

onne

ctio

n

(5) Power Supply Capacities and Power Losses

The following table shows SERVOPACK’s power supply capacities and power losses when using single-
phase 200 V power supply.

∗ The official model number is SGDV-120A11A008000.

Note 1. SGDV-R70A, -R90A, -1R6A, and -2R8A SERVOPACKs do not have built-in regenerative resistors. If the regen-

erative energy exceeds the specified value, connect an external regenerative resistor between B1/ and B2.

2. Regenerative resistor power losses are allowable losses. Take the following action if this value is exceeded.

• Remove the lead or shorting bar between terminals B2 and B3 on the SERVOPACK main circuit of SGDV-

5R5A, -120A SERVOPACKs.

• Install an external regenerative resistor between external regenerative resistor connection terminals B1/ and

B2.

3. External regenerative resistors are not included.

(6) How to Select Molded-case Circuit Breaker and Fuse Capacities

The following table shows the SERVOPACK’s current capacities and inrush current when using single-phase
200 V power supply. Select a molded-case circuit breaker and fuses in accordance with these specifications.

∗ The official model number is SGDV-120A11A008000.

Note 1. To comply with the EU low voltage directive, connect a fuse to the input side as protection against accidents

caused by short-circuits. Select the fuse for the input side that are compliant with UL standards.
The table above also provides the net values of current capacity and inrush current. Select a fuse and a molded-
case circuit breaker which meet the breaking characteristics shown below.
•Main circuit, control circuit: No breaking at three times the current values shown in the table for 5 s.
•Inrush current: No breaking at the current values shown in the table for 20 ms.

2. The following restrictions apply to UL standard compliance conditions for SGDV-120A11A008000 SERVO-

PACKs.
Current rating when using molded-case circuit breaker: 40 A max.

Main Circuit

Power

Supply

Maximum

Applicable

Servomotor

Capacity

[kW]

SERVOPACK

Model

SGDV-

Power Supply

Capacity per

SERVOPACK

[kVA]

Output

Current

[Arms]

Main Circuit

Power Loss

[W]

Regenerative

Resistor

Power Loss

[W]

Control

Circuit

Power Loss

[W]

Total

Power

Loss

[W]

Single-phase,

200 V

0.05

R70A 0.2

0.66

5.2

17

22.2

0.1

R90A 0.3

0.91

7.4

24.4

0.2

1R6A 0.7

1.6

13.7

30.7

0.4

2R8A

1.2

2.8

24.9

41.9

0.75

5R5A

1.9

5.5

52.7

8

77.7

1.5

120A

*

4

11.6

68.2

10

22

100.2

Main Circuit

Power Sup-

ply

Maximum

Applicable Ser-

vomotor

Capacity

[kW]

SERVO-

PACK Model

SGDV-

Power Supply

Capacity per

SERVOPACK

[kVA]

Current Capacity

Inrush Current

Main Circuit

[Arms]

Control Cir-

cuit

[Arms]

Main Circuit

[A0-p]

Control Cir-

cuit

[A0-p]

Single-phase,

200 V

0.05

R70A 0.2

2

0.2

33

70

0.1

R90A 0.3

2

0.2

1R6A 0.7

3

0.4

2R8A

1.2

5

0.75

5R5A

1.9

9

33

1.5

120A

*

4

16

0.25