3.7 Connecting Regenerative Resistors

3-31

3

Wi

ring and

C

onne

ctio

n

(3) SERVOPACKs: Model SGDV-470A, -550A, -590A, -780A, -210D, -260D, -280D, -

370D

No built-in regenerative resistor is provided, so the external regenerative resistor is required. The regenerative
resistor units are as follows:

Note: The regenerative resistor unit is constructed from a number of resistors.

Connect the B1/ and B2 terminals of the SERVOPACK to the R1 and R2 terminals of the regenerative resis-

tor unit.

When using a regenerative resistor unit, leave Pn600 at its factory setting. Set Pn600 when using a non-

YASKAWA external regenerative resistor.

Main Circuit

Power Supply

Applicable

SERVOPACK Model

SGDV-

Applicable

Regenerative

Resistor Unit

Resis-

tance (

Ω)

Specifications

Three-phase
200 V

470A

JUSP-RA04-E

6.25

Four 25

Ω (220 W) resistors are connected

in parallel.

550A, 590A, 780A

JUSP-RA05-E

3.13

Eight 25

Ω (220 W) resistors are connected

in parallel.

Three-phase
400 V

210D, 260D

JUSP-RA18-E

18

Two series of two 18

Ω (220 W) resistors

each are connected in parallel.

280D, 370D

JUSP-RA19-E

14.25

Four series of two 28.5

Ω (220 W) resistors

each are connected in parallel.

Regenerative Resistor Unit

JUSP-RA

-E