3 Wiring and Connection

3.1.4 Using the SERVOPACK with a DC Power Input

3-14

3.1.4 Using the SERVOPACK with a DC Power Input

(1) Parameter Setting

When using a DC power supply, make sure to set the parameter Pn001.2 to 1 (DC power input supported)
before inputting DC power.

Observe the following precautions.

(2) DC Power Supply Input Terminals for the Main and Control Circuits

Three-phase, 200 V for SGDV-

A

(

= R70, R90, 1R6, 2R8, 3R8, 5R5, 7R6, 120, 180, 200, 330)

Three-phase 200-V SGDV-

A

(

= 470, 550, 590, 780)

Three-phase, 400 V for SGDV-

D

(

= 1R9, 3R5, 5R4, 8R4, 120, 170, 210, 260, 280, 370)

Parameter

Meaning

When Enabled Classification

Pn001

n. 0

Enables use of AC power input.

After restart

Setup

n. 1

Enables use of DC power input.

WARNING

• Either AC or DC power can be input to the 200-V, 400-V SERVOPACKs. Always set Pn001.2 to 1 to spec-

ify a DC power input before inputting DC power. Only AC power can be input to the 100-V SERVOPACKs.
If DC power is input without changing the parameter setting, the SERVOPACK’s internal elements will burn and
may cause fire or damage to the equipment.

• With a DC power input, time is required to discharge electricity after the main power supply is turned OFF.

A high residual voltage may remain in the SERVOPACK after the power supply is turned OFF. Be careful

not to get an electric shock.

• Install fuses on the wires if DC power is used.
• Servomotor returns a regenerated energy to the power supply. The SERVOPACK that can use a DC

power supply is not capable of processing the regenerated energy. Provide measures to process the

regenerated energy on the power supply.

• With a DC power input, connect an external inrush current limit circuit.

Failure to observe this caution may result in damage to the equipment.

Terminal Symbols

Name

Specifications

B1/

Main circuit positive terminal

270 to 320 VDC

2

Main circuit negative terminal

0 VDC

L1C, L2C

Control power input terminal

200 to 230 VAC

Terminal Symbols

Name

Specifications

B1/

Main circuit positive terminal

270 to 320 VDC

Main circuit negative terminal

0 VDC

L1C, L2C

Control power input terminal

200 to 230 VAC

Terminal Symbols

Name

Specifications

B1/

Main circuit positive terminal

513 to 648 VDC

2

Main circuit negative terminal

0 VDC

24 V, 0 V

Control power input terminal

24 VDC

±15%