9.1 Alarm Displays

9-21

9

Trou

blesh

ooting

A.E74:
Unsupported Safety

Option Module

A safety option module fault
occurred.

Replace the safety option module.

A unsupported safety option
module was connected.

Refer to the catalog of the con-
nected safety option module.

Connect a compatible safety option
module.

A.E75:
Unsupported Feed-

back Option Module

A feedback option module fault
occurred.

Replace the feedback option mod-
ule.

A unsupported feedback option
module was connected.

Refer to the catalog of the con-
nected feedback option module or

the manual of the SERVOPACK.

Connect a compatible feedback
option module.

A.EA2:
DRV Alarm 2
(SERVOPACK WDT
error)

MECHATROLINK transmission
cycle fluctuated.

Check the MECHATROLINK
transmission cycle setting.

Remove the cause of transmission
cycle fluctuation at host controller.

A SERVOPACK fault occurred.

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be

faulty. Replace the SERVOPACK.

(cont’d)

Alarm Number:

Alarm Name

(Alarm Description)

Cause

Investigative Actions

Corrective Actions